Struthers-Dunn - Item # M60A-24D, 35/60 Series - Mercury Displacement Power Relays

Call Us  843.664.3303  |  E-Mail Us    

Struthers-Dunn - Leaders in Relays & Controls Since 1923
Manufacturer of High Quality Relays & Controls
Relays & Controls
  GO

Relay Products ____

General Purpose Power Contactors Motor Reversing Latching/Sequencing Special Purpose & Custom Design Sensitive - Low Input Power Timer/Sensor Reed Accessories and Sockets Inventory Locator

 
Home Product Catalog Literature Sales Channels Industries Served About Us News RFQ/RFI Contact
Inventory Locator

All Categories > Accessories and Sockets > Industrial 12 & 14 Pin Socket > 545 Series - Screw Terminal Latching Contactors > 286/287 Series - Squre Base Time Delay Relays > 502 Series - Latching Contactors > 575 Series - Motor Reversing Contactors > 21/136 Series - Transfer General Purpose Relays > 35/60 Series - Mercury Displacement Power Relays > Item # M60A-24D  
    Download PDF Download PDF     Print Printable Page     Email Email This Page     Save To Favorites Save To Favorites
Request Information

Item # M60A-24D 35/60 Series - Mercury Displacement Power Relays



    Download PDF Download PDF  
    Email Email This Page  
    Save To Favorites Save To Favorites
  


The 35 & 60 series products are mercury displacement relays. Sealed tubes containing liquidmercury assure contact surfaces are freshly replenished with every contact movement. Contactresistance is among the lowest available for any electromechanical relay. The M35 series offerssuperior long life performance. Products are available with 1, 2, or 3 poles rated 35 amps. Contactscan be normally open or normally closed.

Optional DIN rail adaptors – 1 pole = 16-MDRDIN-1, 2 or 3 pole = 16-MDRDIN-2/3

For Additional Configuration please contact the manufacturer.


35/60 Series - Mercury Displacement Power Relays

larger image

35-Series_1pole_dim

larger image



Specifications · Contacts · Coil · Timing · Dielectric Strength · Temperature · Life Expectancy · Miscellaneous

Specifications

Series

M60

Contact Arrangement

A (1 N.O. tube)

Coil Voltage

24 VDC


Contacts

Contact Configuration

Up to 3PST

Contact Material

Liquid Mercury

Contact Rating

60 A

Contact Rating 120 / 240VAC Resistive

60 A

Contact Rating 28VDC Resistive

60 A

Motor 120VAC 1 Phase

5 hp

Motor 240VAC 1 Phase

10 hp

Contact Resistance, Initial

50 milliohms max at 6VDC


Coil

Coils Available

AC and DC

Nominal Coil Power AC

7 to 28 VA

Nominal Coil Power DC

3 to 9 W

Input Voltage Tolerance - AC

85% to 110% of nominal

Input Voltage Tolerance - DC

80% to 110% of nominal

Drop-out voltge

10% of nominal

Duty

Continuous


Timing

Operate Time (max)

50 ms

Release Time (max)

80 ms


Dielectric Strength

Across Open Contacts

2650 Vrms

Between Mutually Insulated Point

2650 Vrms

Insulation Resistance

1000 megohms at 500VAC


Temperature

Operating

-34 to 74 ºC
-30 to 165 ºF

Storage

-40 to 105 ºC
-40 to 221 ºF


Life Expectancy

Electrical (full load)

250,000

Mechanical (no load)

5,000,000


Miscellaneous

Mounting Position

Vertical within 10 degrees

Enclosure

Hermetically Sealed

Weight

Varies